RemoteConnect error "DTMS not found in the catalog"

After installation, if RemoteConnect is launched and it reports the following error:
DTM1

This can occur if RemoteConnect DTMs are not installed correctly.
DTM error

Solution:

  • To update the catalogue, try clicking the update catalogue button.
  • The installation file for RemoteConnect must be located on the local drive C:.
  • Make sure that the downloaded zipped file is unblocked (2-RemoteConnect-R-2.7.3_Ecostruxure-Control-Expert-V-15.1.zip in the screen capture below)

unblocked

  • Verify under the C:\Program Files (x86)\Common Files that the FDT and Schneider Electric Shared are complete.

FDT
SE shared folder

Schneider Electric Belgium

Ontdek meer
Product:
Productfamilie
Ontdek meer
Product:
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings