How to enable the datalogging service of a BMENOR2200H RTU module?
Issue:
How to enable the datalogging feature on the BMENOR2200 RTU module and make It available on its webpage.
Product Line:
BMENOR2200H RTU module
Environment:
- EcoStruxure Control Expert V15.0 with “ControlExpert_V150_HF_Integrity_check” and “ ControlExpert_V150_HF_BMENOR2200H” installed, or EcoStruxure Control Expert V16.0 & later.
- BMENOR2200H SV3.01.07 firmware & above.
Resolution:
The datalogging service becomes available on the BMENOR2200H RTU module since its firmware version SV3.01.07 and later , using EcoStruxure Control Expert V15.0 and above:
To make the datalogging service available, It is mandatory to select the BMENOR2200.2 or BMENOR2200.3 in the hardware configuration of the project:
The datalogging will be then available on the DTM of the BMENOR2200H:
And also accessible from its webpage: