How to manually check and correct Auxiliaries from older project which are not compatible due to new offer Auxiliary Acti9 and Multi9 evolution in V2.5.XX in EcoStruxure PowerBuild – Rapsody.
Product Line: EcoStruxure Power Build – Rapsody
Resolution:
With the new version V2.5.X of EcoStruxure PowerBuild- Rapsody, as the Auxiliaries Acti9 and Multi9 have evolved, it will cause a compatibility breach in EcoStruxure Power Build Rapsody when working on new version V2.5.X with project created in older version V2.1.X which had OF-SD selected for the following offers:
| C120 |
| iC60 |
| iC60 double terminals |
| Acti9 C60H-DC |
| iSW NA |
| iDPN N Vigi |
| iDPN H Vigi |
| iDPN N Vigi G type |
| ACTI9 iC40 |
| ACTI9 iCV40 Feeder |
| ACTI9 iID40 |
| ACTI9 iIG40 |
| ACTI9 iDT40 |
| ACTI9 iDD40 Head of group |
| ACTI9 iDD40 Feeder |
Step1:
Open the old project SSD file in version V2.5.X by using the option “Open an Existing Project” or “Open a recent Project”.
Step2:
When pop-up for project update appears, choose “No”.
Step3:
From “Electrical Organization” tab, Generate functional Names as shown in below screenshot.
Step4:
Click on Update project button
Step5:
Export the list or save the screenshot for each impacted switchboard.
Step6:
Go to Product Choice and right click on the impacted devices and choose “Modify” and select the required characteristics. Modify the impacted devices for all the switchboard.
Note: For project with more number of switchboard and devices with auxiliaries, it may take longer time to validate the devices.
Gepubliceerd voor: Schneider Electric Belgium
Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.