What can cause an Internal Error 10 on the ATS480 soft start?

Issue:

What can cause an Internal Error 10 on the ATS480 soft start?

Product Line:

ATS480

Environment:

INF10 fault

Cause:

n/a

Resolution:

Would suggest to power down the soft start and recheck all the internal connections.

This error is triggered if the external +24vdc supply voltage is higher than 30v, or lower than 19v.

This fault can also occur if the 24v output current is greater than 200ma.

Measure the +24v to com on the soft start.

Check the +24Vdc supply or the current requested by the load connected to the output +24

Recheck the wiring: Previous wiring of ATS48 (+24 and LO+) is at the same location (+24 and 0V) for ATS480.

Do not connect LO+ from ATS48 to 0V of the ATS480.

Schneider Electric Belgium

Ontdek meer
Product:
Ontdek meer
Product:

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings