{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.

Populaire vragen (FAQ's) zoeken

Can I-line II busway be installed under a raised floor?

Issue:

Needs to install busway under a raised floor

Product Line:

Busway

Environment:

I-line II Busway

Cause:

N/A

Resolution:

Our I-Line II busway can be installed under "raised floors" as long as the busway joints and support system are accessible and the space is not used as return air systems.

Schneider Electric Belgium

Ontdek meer
Productfamilie
I-Line Busway
Ontdek meer
Productfamilie
I-Line Busway