What would cause the ATV680 AFE drives to show incorrect line voltage measurements on the HMI?
Issue:
ATV680 AFE drives is showing incorrect line voltage measurements on the HMI?
Product Line:
ATV680 and ATV980 enclosed drives.
Environment:
All
Cause:
Loose wiring connection, blown fuse etc.
Resolution:
If the input Line voltage is measuring the correct line voltage phase to phase and to ground.
Remove power and check the following:
-Check the main power fuses they have a tab that will popout to show if they are blown.
-Check the L1 L2 L3 input fuses on the RFI filter circuit board (bottom right corner of ATV680 enclosure if you're facing the drive)
-Check for loose wires on the L1 L2 L3 terminals of the RFI filter circuit board.
-Hire field services to come out and check or replace the RFI circuit board or the Power board.
Example of incorrect input or line voltage readings on the HMI> Drive is running and or in IDLE mode.
Main menu
Display menu
Drives Parameters
Mains voltage 338vac
L1= 239vac is incorrect (480vac is correct reading)
L2= 239vac is incorrect (480vac is correct reading)
L3= 480vac is the correct reading
DC bus= 680vdc (Running)
DC bus= <20vdc (IDLE mode)
In this example the L2 wire was disconnected on the RFI filter board.
Gepubliceerd voor: Schneider Electric Belgium
Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.