Can the BMENUA0100 get variables time stamped at the source ?
The sources accepted to provide such data are BMXERT modules, RIO (via BMECRA3210), internal Bool variables managed by the application, and data coming from external sources.
- This requires to use EcoStruxure Control Expert V15.2 or later, with an M580 CPU firmware V 4.10 or later.
- We must choose the BMENUA0100.2 in the hardware configuration of the project:
- The "Source timestamping " option must be enabled in the NUA module configuration:
- The time stamping mode must be configured on "system" in the project setting and the "max events stored" must be different than 0 :
- The time stamping of variables should be correctly configured in the data editor ( "both edges" in this example) :
More details can be found on this video: https://www.youtube.com/watch?v=jRlf0NTZV_A