Power Quality Performance Module Not Showing Data
Issue
The Power Quality Performance Module is not updating. Event logs do not update. Status objects on diagram do not reflect changes.
Product Line
Power Quality Performance Module
Environment
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Cause
- There has been a recent change to the certificate binding, restricting the HTTP port and enabling the HTTPS port.
- The local server address in the SQL server database has been hardcoded.
Resolution
Before continuing, confirm that VIP.PQADVISOR has been correctly configured.
Resolution 1:
- Verify that all steps were taken in FA309041 to restrict HTTP port access and enable HTTPS access. Particularly, check that the web config file has been properly commented to reflect changes.
-
-
- Verify that the ION_Network and Application_Modules database has been reconfigured so that the local server address reflects the proper domain name.
- Example:
- Example:
- Confirm that HTTPS binding has been deleted from the site bindings.
- Confirm host is pointing to the correct domain name.
Resolution 2
- Open Designer. Navigate to VIP.PQADVISOR.
- Confirm that each XML Import Module reflects the correct URL address.
- Reinitialize the diagrams.
Gepubliceerd voor: Schneider Electric Belgium
Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.