Can sleeves be used on busbars in PrismaSeT I?

PrismaSeT I System M switchboard comply with the IEC 61439-1/2 edition 2 requirements. Insulation by sleeves for busbars is not recommended and it is not a standard solution in PrismaSeT switchboard. All the panels which are type tested are with bare busbars.

Heat shrinkable sheathing temperature is usually limited to 105°C. Over this temperature limit, heat shrinkable sheathing tends to crack (self-constraint due to its heat-shrinkable feature). When cracking, over time, this insulation material may create a creepage way between two phases, thus potentially generating phase to phase flashover (internal arc).

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings