The crash occurs when EPC-M version 2.2.0 is used with PAS firmware version 2.3.0 and the user selects the "Skip Password" option. This behavior is due to incompatibility between these versions and a failure to meet the RED DR cybersecurity compliance requirements.
To avoid this issue:
- Upgrade EPC-M to version 2.3.0 when using PAS 2.3.0.
- If using EPC-M 2.3.0 with PAS 2.2.0, it is recommended to upgrade PAS to version 2.3.0 for full compatibility and RED DR compliance.
Firmware Compatibility Table
SL No | EPC-M Version | PAS FW Version | RED DR Compliance | Comments | Recommendation |
---|---|---|---|---|---|
1 | 2.2.0 | 2.2.0 | NA | SKIP Password option available | NA |
2 | 2.3.0 | 2.3.0 | Fully Compliant | It is mandatory to set a password. | NA |
3 | 2.2.0 | 2.3.0 | Non-Compliant | The app may crash when "Skip Password" is selected | Upgrade EPC-M to version 2.3.0 |
4 | 2.3.0 | 2.2.0 | Partial | Recommended upgrade for stable support | Upgrade PAS firmware to version 2.3.0 |