Troubleshooting SAGE 4400 RTU Using LED Indicators
Issue:
How to interpret LED indicators on the SAGE 4400 RTU for troubleshooting purposes.
Product:
SAGE 4400 RTU
Environment:
Substation automation systems using SAGE 4400 RTU for monitoring and control.
Cause:
Users may encounter operational issues and need a quick method to diagnose problems without advanced tools.
Resolution:
The SAGE 4400 front panel includes LEDs that provide real-time status for communication ports and system conditions:
- Comm LEDs (per RS232 port):
- DCD/+5V: Data Carrier Detect or +5V output
- RX: Receive activity
- TX: Transmit activity
- RTS: Request to Send
- CTS: Clear to Send
- System LEDs:
- Power: Indicates RTU power (normally ON)
- Run: CPU running (blinking = normal; steady ON = Safe/Recovery mode; OFF = CPU not running)
- Reset: Illuminates during reset signal (normally OFF)
- Local: Indicates Local/Remote switch position (Local disables controls)
- Time Source Failed: Configured time source failure
- IED Failed: Communication failure with one or more IEDs
- Alarm 1 & 2: Relay energized status
- User Logged In: Active user session
- Config Changed: New configuration XML file loaded but not yet activated
- RLL Running: ISaGRAF logic program active
- Ethernet Link: Valid Ethernet connection detected
Use these indicators to quickly identify power, communication, configuration, or control issues before performing deeper diagnostics.
Gepubliceerd voor: Schneider Electric Belgium
Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.