How to perform self-test on Back-UPS products?
Issue: Understanding the operation of the Back‑UPS self‑test and what happens during the test.
Product Line: Back‑UPS/Back-UPS Pro products
Cause: Users may need to test the battery inside the UPS to check battery condition.
Resolution:
By default, Back‑UPS units automatically perform a self‑test each time they are powered on to check battery condition and estimate runtime. During the self‑test, the UPS briefly switches to battery power for about 10 seconds, then returns to normal AC operation. For accurate results, the connected load should be between 10% and 30% of the UPS’s rated capacity, as lighter or heavier loads may lead to inaccurate runtime estimates.
For more details, see Back‑UPS Basic Self‑Test Theory Explained.
DISCLAIMER: If the self‑test is performed incorrectly or if unsupported methods are used, there is a risk of dropping the connected load.