Issue
In reporter attempting to change the date range under manage reports results in the below error:

Product Line:
PME 7.2.x
Environment
Reporter
Cause
The format for the values in the STIME (start time) and ETIME (end time) columns in the [PRIVATE] Datasheets tab is not configured as per the reporter's requirement.
Resolution
i) Navigate to the folder where the report is being stored on the computer. The default path is C:\Program files (x86)\Schneider Electric\Power Monitoring Expert\Config\Reports.
ii) Double-click the report file with the issue, to open with Microsoft Excel.
iii) Click on the workbook "[PRIVATE]Datasheets"
iv) Change the format for the column labeled "STIME" and "ETIME" from 00.00.00 to 00:00:00 i.e instead of using a . change it to a :

In reporter attempting to change the date range under manage reports results in the below error:
Product Line:
PME 7.2.x
Environment
Reporter
Cause
The format for the values in the STIME (start time) and ETIME (end time) columns in the [PRIVATE] Datasheets tab is not configured as per the reporter's requirement.
Resolution
i) Navigate to the folder where the report is being stored on the computer. The default path is C:\Program files (x86)\Schneider Electric\Power Monitoring Expert\Config\Reports.
ii) Double-click the report file with the issue, to open with Microsoft Excel.
iii) Click on the workbook "[PRIVATE]Datasheets"
iv) Change the format for the column labeled "STIME" and "ETIME" from 00.00.00 to 00:00:00 i.e instead of using a . change it to a :
Released for: Schneider Electric Canada


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.