Can the factory leads of the SDSA1175 surge protective device be extended by splicing or adding conductor length, without violating manufacturer specifications or affecting device performance?

Issue:
Can the SDSA1175 leads be lengthened without affecting compliance or performance?

Product Line:
Surge Arrestors

Environment:
SDSA1175

Resolution:
No. To ensure optimal performance, the SDSA1175 should be installed as close as possible to the protected circuit to minimize lead length. Each additional foot of conductor can introduce approximately 160 V of let-through voltage (based on a 6 kV / 3 kA, 8/20 µs surge). The device’s Voltage Protection Rating (VPR), as tested per UL 1449 standards, is measured six inches from the enclosure. Square D does not recommend extending the leads, as doing so may alter the clamping voltage from published specifications.

Schneider Electric Canada

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings