Can the Series 300 (with the new Group G controller) be used on a different voltage system?
Answer: Yes, a Series 300 (with the new Group G controller) be used on a different voltage system after some changes are made.

HOWEVER, the following parts below MAY need replacing.
  1. Group G controller
  2. Transfer Switch Coil

Furthermore, dipswitch settings and voltage jumper positions must be set properly.

A Group G controller has three (3) part numbers and are rated for certain nominal voltages.
  1. PN 894000-001 – 115V and 120V
  2. PN 894000-002 – 208V, 220V, 230V, 240V, 380V, 400V, 415V, 440V, 460V, and 480V
  3. PN 894000-003 – 277V, 550V, 575V, and 600V

A transfer switch coil is also rated for a certain voltage range. For example, a coil assembly can be rated for 190-240V.

So, if a transfer switch came rated at 3-phase 208V and the customer decided to use it on a 1-phase 240V system, they won’t have to replace any part.  They just need to change some settings (See Dipswitch tables below).

But, if the transfer switch came rated for 3-phase 480V and they need to use it on a 3-phase 208V system, then they need to replace the Group G controller and the transfer switch coil.

Group G Controller Part Number and Jumper Card Position

Group G Controller Phase Configuration Dipswitch Setting

Group G Controller Nominal Voltage Dipswitch Setting

If unsure, contact Technical Support at 1-800-800-ASCO or send an email to technicalsupport@ascopower.com

Schneider Electric Canada

Can the Series 300 (with the new Group G controller) be used on a different voltage system?
Answer: Yes, a Series 300 (with the new Group G controller) be used on a different voltage system after some changes are made.

HOWEVER, the following parts below MAY need replacing.
  1. Group G controller
  2. Transfer Switch Coil

Furthermore, dipswitch settings and voltage jumper positions must be set properly.

A Group G controller has three (3) part numbers and are rated for certain nominal voltages.
  1. PN 894000-001 – 115V and 120V
  2. PN 894000-002 – 208V, 220V, 230V, 240V, 380V, 400V, 415V, 440V, 460V, and 480V
  3. PN 894000-003 – 277V, 550V, 575V, and 600V

A transfer switch coil is also rated for a certain voltage range. For example, a coil assembly can be rated for 190-240V.

So, if a transfer switch came rated at 3-phase 208V and the customer decided to use it on a 1-phase 240V system, they won’t have to replace any part.  They just need to change some settings (See Dipswitch tables below).

But, if the transfer switch came rated for 3-phase 480V and they need to use it on a 3-phase 208V system, then they need to replace the Group G controller and the transfer switch coil.

Group G Controller Part Number and Jumper Card Position

Group G Controller Phase Configuration Dipswitch Setting

Group G Controller Nominal Voltage Dipswitch Setting

If unsure, contact Technical Support at 1-800-800-ASCO or send an email to technicalsupport@ascopower.com  

 

Schneider Electric Canada

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.