Tesys Island Download not possible error message
Issue:
Unable to load the configuration to bus coupler TPRBC*** from Somove.
Unable to download
Product Line:
Tesys Island Motor Management System

Environment:
IEC Contactors and Relays

Answer:
This message is shown if the DTM tries to store a configuration to the Bus Coupler but it is rejected.  This could happen if there is a mismatch between versions of the DTM and the Bus Coupler firmware.  Check the compatibility matrix from the Release Notes and verify that your DTM and Firmware version match.
This message will also display if the Bus Coupler reference is inconsistent, i.e. storing a configuration for a Profinet bus coupler (TPRBCPFN) on an EtherNet/IP bus coupler (TPRBCEIP).
@media (prefers-color-scheme:dark) {.apath {fill: #fff}}
Improve
CtrlD

Schneider Electric Canada

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings