500 Vdc Thermal Magnetic Circuit Breakers - LHL-DC
Direct Current (dc-rated) Circuit Breakers
Features
- Voltage Ratings: 500 Vdc nominal, 600 Vdc floating maximum voltage
- AIR: 20 kA
- CSA C22.2 No. 5-02 / UL 489 Supplement SC rated specifically for use on ungrounded dc systems and Uninterruptible Power Supplies (UPS)
- Industry leading low magnetic trip setting for improved short-circuit protection
- 250A as low as 625 dc amperes
- 300A as low as 750 dc amperes
- 350A as low as 875 dc amperes
- 400A as low as 1000 dc amperes
- Factory installable accessories available – see catalog
- Easily accessible adjustable magnetic trip on front face of breaker
LHL3625025DC – 250A, 600V, 3 pole circuit breaker with a dc amperage range from 625 to 1250 A
LHL3630026DC – 300A, 600V, 3 pole circuit breaker with a dc amperage range from 750 to 1500 A
LHL3635029DC – 350A, 600V, 3 pole circuit breaker with a dc amperage range from 875 to 1750 A
LHL3640030DC – 400A, 600V, 3 pole circuit breaker with a dc amperage range from 1000 to 2000 A