Issue:
Where can I find the contact rating of part #s 9999SX11 and 9999SX12.
Product Line:
8502 Contactors and 8536 Starters
Environment:
NEMA Contactors and Starters
Resolution:
These contacts are designed for AC applications only. The following ratings are based on 35% power factor and voltage specific.
120 volts or less = 30 amp make, 3 amp continuous, 3 amp break.
120 to 600 volts = 3600 VA make, 3 amp continuous, 360 VA break.
Where can I find the contact rating of part #s 9999SX11 and 9999SX12.
Product Line:
8502 Contactors and 8536 Starters
Environment:
NEMA Contactors and Starters
Resolution:
These contacts are designed for AC applications only. The following ratings are based on 35% power factor and voltage specific.
120 volts or less = 30 amp make, 3 amp continuous, 3 amp break.
120 to 600 volts = 3600 VA make, 3 amp continuous, 360 VA break.