Vores varemærker

Impact-Company-Logo-English Black-01-177x54

Velkommen til Schneider Electrics website

Velkommen til vores website
		
Hvordan kan vi hjælpe dig i dag?
What is the difference between ModSoft PID function and Concept PID function.

The difference between ModSoft PID and Concept PID loops are as follows:

PID (ModSoft):
PB - Gain = 100 / PB
I - Integral Coefficient Expressed as Repeats/Minute. The higher the value, the greater the integral contribution
D – Derivative Coefficient. Expressed in Minutes. The higher the value, the greater the derivative contribution
PID (Concept):
GAIN - Enter GAIN value as a REAL. Can be Positive or Negative. Positive Gain = Direct acting loop. Negative Gain = Reverse acting loop
TI - Integral Time. Expressed as TIME. The smaller the unit of time, the more significant the integration
TD - Derivative Time. Expressed as TIME. The greater the unit of time, the greater the derivative contribution.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger