What is the meaning of OC1 fault in Altivar 21 Drive.

The meaning of OC1 is over current during Acceleration. This fault appears when the motor is drawing excess current during acceleration.

Main probable causes of the fault:
1         The acceleration time ACC is too short.
2         The parameter Pt(Motor Control Mode) is incorrect.
3         The drive is starting into a rotating load.
4         A special motor (e.g. motor with small impedance) is used.
Remedies:
1         Increase the acceleration time
2         Check the Pt (Motor Control Mode) parameter.
3         Use F301 (Auto-Restart) and F302 (Coast Stop).
4         Adjust the switching frequency F300.
5         Set parameter F316(Switching Frequency Control Mode) to 1 or 3 (carrier frequency is decreased automatically).

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger