Issue:
Programming and wiring needed for ATS22 3-wire control.
Product Line:
Altistart 22
Environment:
All
Cause:
Installation
Resolution:
Wiring:
Wire a momentary normally-closed STOP contact to LI1 and a momentary normally-open START contact to LI2.
Programming:
Set LAC= On
In the I-O menu, set LI2 to Start (3 wire control).
Programming and wiring needed for ATS22 3-wire control.
Product Line:
Altistart 22
Environment:
All
Cause:
Installation
Resolution:
Wiring:
Wire a momentary normally-closed STOP contact to LI1 and a momentary normally-open START contact to LI2.
Programming:
Set LAC= On
In the I-O menu, set LI2 to Start (3 wire control).