Video: How can you program the ATV212 drive to follow 0-10vdc speed signal on VIA and start/stop via terminal control?
Issue:
ATV212 programming to follow 0-10vdc speed signal on VIA and start/stop via terminals
Product Line:
Altivar ATV21 and ATV212
Environment:
All
Cause:
Wants to use VIA for 0-10vdc speed control and start stop via 2 wire control thru the terminal inputs.
Resolution:
SW100 switch setting: Set the switch on the main circuit board to U for an 0-10vdc input signal for VIA (set upper switch to the left position)
Wiring:
0-10vdc signal to VIA and CC
Two wire start dry contact or relay is wired between P24 and F
Programming:
FNOD= 1 VIA
CNOD= 0 (terminal control)
F111= 2 for 2 wire control
uLu= motor voltage
F415= normal motor current
F417= normal motor RPMs
thr = normal motor current
ATV212 programming to follow 0-10vdc speed signal on VIA and start/stop via terminals
Product Line:
Altivar ATV21 and ATV212
Environment:
All
Cause:
Wants to use VIA for 0-10vdc speed control and start stop via 2 wire control thru the terminal inputs.
Resolution:
SW100 switch setting: Set the switch on the main circuit board to U for an 0-10vdc input signal for VIA (set upper switch to the left position)
Wiring:
0-10vdc signal to VIA and CC
Two wire start dry contact or relay is wired between P24 and F
Programming:
FNOD= 1 VIA
CNOD= 0 (terminal control)
F111= 2 for 2 wire control
uLu= motor voltage
F415= normal motor current
F417= normal motor RPMs
thr = normal motor current
Udgivet til: Schneider Electric Danmark
Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.