Can you switch between 2 wire control and 3 wire control using a logic input?

Issue:
Change between 2 wire control and 3 wire control with logic input.

Product Line:
Altivar 61, ATV61

Environment:
All models, All serial numbers.

Cause:
none

Resolution:
The drive must be programmed as either 2 wire or 3 wire control.  There is no way to change this without both programming and wiring changes to the drive.

2 wire control - LI1 is run forward.  The default programming is a transition of LI1 from low to high in order to run.  This can be changed to Level switching.  LI1 must stay closed for the drive to run.
3 wire control - LI1 is stop (NC contact) and LI2 is run forward.  A momentary or maintained closure of LI2 causes the drive to run forward.  LI1 (stop) needs to be opened in order to stop the drive.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger