When replacing and ATV66 with a ATV61/71, what are the control wiring considerations?

Issue:
Control wiring considerations when replacing an ATV66 with a ATV61/71

Product Line:
Altivar 66

Environment:
All releases

Cause:
Replacing drives.

Resolution:
When converting the wiring to the Altivar 61/71 drive, discard the wires on CL1 and CL2 (ATV66) , not used on the ATV61/71.
Also the run permissive and run forward are swapped around, between the ATV66 and ATV61/71.
ATV66:        LI1 = run permissive and LI2 = run forward
ATV61/71:   LI1 = run forward and LI2 = run permissive (nSt)  (run permissive, if used assign freewheel stop nSt (Fun Menu 1.7) to LI2))
Most other terminations will be the same.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger