Video: How do I change from ramp stop to freewheel stop on the ATV61 and ATV71 drives?
Issue:
Programming Freewheel Stop on Altivar 61 & 71 Drives

Product line:
ATV61, ATV71

Environment:
All models, all serial numbers

Cause:
Need to change the stop type to support application.

Resolution:
  • Go into the Application menu 1.7
  • Enter Stop configuration
  • Enter " type of stop"
  • Change SST (type of stop) value to NST and enter.
Additional  resources (attached):  ATV71 programming manual  and ATV61 programming manual.

type of stop

Schneider Electric Danmark

Bilag
ATV61_Programming_manual_EN_1760649_09.pdf [2.37 MB]
ATV71_Programming_manual_EN_1755855_10.pdf [5.94 MB]
Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger