Hvordan kan vi hjælpe dig i dag?

What is a TJF fault on the ATV61 and ATV71 drives?

Issue:
TJF fault on the ATV61/ATV71 drives

Product Line:
Altivar ATV61 and ATV71

Environment:
All

Cause:
TJF means IGBT overheating caused by drive overheating

Resolution:
This fault appears when the estimated temperature of an IGBT is too high.  It is a calculated measurement based on the switching frequency, drive output frequency, and motor current.
Check the size of the load, motor, and drive.
Reduce the switching frequency in menu 1.4
Wait for the motor to cool before trying to restart the drive.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

Brug for hjælp?

Produktvælger

Produktvælger

Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

Få et tilbud

Få et tilbud

Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

Find forhandler

Find forhandler

Find den nærmeste Schneider Electric-distributør.

Hjælpecenter

Hjælpecenter

Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger