What are the instantaneous operating times of a protection function?
The Sepam series 20 and series 40 manuals give the operating time for 2 types of outputs:
- pick-up which is the non-confirmed instantaneous output: e.g. for phase O/C 50/51, T<35ms
- instantaneous which is the output that can be used for tripping: this is the confirmed instantaneous operating time: e.g. for phase overcurrent protection 50/51, T<50ms
Note:
- pick-up time is included in the specified operating time (the 2 times are not added together)
- pick-up time is common to all the non-confirmed outputs of the protection functions in operation, according to the parameter setting of the matrix
Udgivet til: Schneider Electric Danmark


Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.