How do I set the Time of Day(TOD) clock in the SY/MAX PLCs?

Issue

How do I set the Time of Day (TOD) clock in the SY/MAX PLCs?

Product Line

TSX Micro

Environment

Sy/Max

Resolution

To set the TOD clock in a SY/MAX controller first enter a value of "-1" into register 8108, then enter the new values into the remaining TOD clock registers (8109-8115). Finally to update and restart the TOD clock enter a value of "0" into 8108. The following table illustrates the SY/MAX TOD clock registers and their function:

REGISTER
FUNCTION
DECIMAL RANGE
8108
SET CLOCK
-1 (set), 0 (normal), 1(stop watch)
8109
Seconds
0-59
8110
Minutes
0-59
8111
Hours
0-23
8112
Day of Week
1-7 (1= Sunday)
8113
Day of Month
1-31
8114
Month
1-12
8115
Year
1980-2079

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger