What could cause my Quantum 140CPU67160 to come up as 'NO CONFIG' after a power cycle?
Issue:
What could cause my Quantum 140CPU67160 to come up as 'NO CONFIG' after a power cycle?
Product Line:
Quantum 140CPU67160
Resolution:
One possible cause is that the PLC is using a PCMCIA card in slot 1 that has a bad battery. A bad battery is indicated by PCM1 with the number flashing on the LCD display. In PLC logic, %S67 (PCMCIABAT0) can be monitored.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance: