Product Line
CM4000 and CM3000
Environment
Registers on the front display.
Resolution
To Read/Write to a register follow the procedure below:
- From the Front Panel Main Menu, select Diagnostics
- Select Read/Write Regs. The password prompt displays.
- Select your password. The default password is 0.
- The Read/Write Registers Screen displays. The table below explains the different formats.
- To scroll through the register numbers use the arrow buttons
- To change the value in the register, press the enter button.
- The Hex and Dec values begin to blink.
- Use the arrow buttons to scroll through the numeric values.
- When you are finished making changes to that register, press the enter button to continue to the next register or press the menu button to save the changes.
Option | Available Values |
Reg | List the register numbers. |
Hex | List the hexadecimal value of that register. |
Dec | List the decimal value of that register |
*NOTE: Some circuit monitor registers are read/write and some are read only. You can write to read/write registers only.
See the attached document for the original instruction release which also works for the CM3000 as well.