The VAUX input of the 3720 is not viewable, by default, on the meter's front panel display. To view this parameter, you will need to configure the meter as follows:
- Connect to the 3720 in ION:Setup (Network setup mode).
- Double click on the Group Keys option.
- It is your choice which group key you wish to have VAUX attached too, my example pictures add the value to Group1 Key (see front panel of the meter for the Group1/2 keys). Select the desired tab.
- Click the insert button.
- Setup the value as this example:
The VAUX value should show up in the list as below: