Can I use AB1AL** (Common Link) to the AB1TP435U as well??
Goals and Symptoms
Can I use AB1AL** (Common Link) to the AB1TP435U as well??
Facts and Changes
Common link
Protective Earth terminal block
Causes and Fixes
It is not necessary to have a common link, because the connections of terminal block for protective earth are electrically connected to the rail. The rail is making the common link.