Setting up the 3720 ACM in PME
Issue:
How to setup and connect a 3720 ACM with ethernet option in ION Enterprise/PME
Product Line:
ION Enterprise
Power Monitoring Expert 7.2
Power Monitoring Expert 8.x
Power Monitoring Expert 9.x
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment:
3720 ACM
Resolution:
1) Open Management Console and add a new ethernet device then add all configurations; group, name, device type, and IP Address like normal.
2) On the same ethernet device configuration page right click in the white area (Highlighted in red) and select Advanced Properties.
3) Change the TCP/IP Port to 3720 ACM with MPE|3721 which should be an option in the drop down menu.
4) Click OK to finish