The Transformer Factor is multiplication of the P1 Ratio (PT Ratio) and the F1 Ratio (CT Ratio). This value is set using the TstBench Software during the 6300 commissioning.
| IF CT ratio is 600:5 and IF PT ratio is 120:120 CT ratio (F1) = 120 PT ratio (P1) = 1 Transformer Factor = F1 * P1 in this case = 120 * 1 = 120 In the TstBench software, the Transformer Factor for 120 is decoded as shown below: Make the Transformer Factor of 120 into 6 digits by adding 0's to the front of the number if necessary (i.e. 000120) The 2 most significant bits are the 2 least significant bits of the transformer factor in the TstBench software (i.e. 00) The next 2 digits, 01 will be the next 2 digits of your number (i.e. 0100) Repeat for the next 2 digits, 20 (i.e. 200100) Transformer factor in Software = 200100 Or Transformer Factor of 2452 Transformer factor in Software = 522400 Or Transformer Factor of 123456 Transformer Factor in Software = 563412 |
Date Created: December 1, 2009
Last Revised: December 28, 2009
Public
Original Author: LA