Audit in the PowerLogic SCADA Event Log for User Logins and Logouts

As of PowerLogic SCADA v7.10 r01.2 (Service Release 2), there is no built in functionality to track user logins and logouts. For those wishing to keep a record, this entry presents one possible solution.
For each user in the project, configure the following parameters in the System > Users window.

Entry Command: PLSAlmDspEventAdd(0, 0, 1, "User Login", Name(), "Login", "");

Exit Command: PLSAlmDspEventAdd(0, 0, 1, "User Logout", Name(), "Logout", "");

The screen capture below shows an example of the output of these functions when user "a" logs in or logs out.


Legacy KB System (APS) Data: RESL202998 V1.0, Originally authored by AnVa on 07/28/2010, Last Edited by AnVa on 07/28/2010
Related ranges: PowerLogic SCADA 7.1

Schneider Electric Danmark

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger