How to connect Unity Pro to a Modbus PLC through a TSXETG100 Ethernet gateway

Issue

How can Unity Pro connect to a Modbus PLC through a TSXETG100 Ethernet gateway?

Product Line

  • TSXETG100
  • Unity Pro

Environment

The TSXETG100 is used as the communication gateway between Unity Pro and the PLC.

Resolution

  1. Configure the PLC Modbus address in the TSXETG100

    • Open the TSXETG100 web interface by entering its IP address in a web browser.

ETG0100, connection

      • Log in to the TSXETG100.
      • Select Setup > Device List.

web page, ETG,

      • Add the Modbus address of the PLC to the device list.
      • Select Apply to save the configuration.
  1. Configure the PLC address in Unity Pro

    • Open the Unity Pro project.
    • Select PLC > Set Address.
    • unity Pro, Set address
    • In Media, select TCPIP.
    • In the Address field, enter the TSXETG100 IP address followed by a semicolon (;) and the PLC Modbus address.
    • connection configuration

    In this example:

    • 192.168.40.2 is the TSXETG100 IP address.
    • 1 is the Modbus address of the PLC.
  2. Connect to the PLC

    • Confirm the address configuration.
    • Select PLC > Connect.


Schneider Electric Danmark

Se mere
Område:
Se mere
Område:
  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Projektrådgivning
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Generelle forretningsbetingelser
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger
  • Præferencecenter