How to round up value when displaying data log in ION Enterprise, SPM, and PME Vista

Issue:
The customer does not want accuracy higher than whole number values.

Product Line:

ION Enterprise
StruxureWare Power Monitoring (SPM)
Power Monitoring Expert (PME)

Environment:
Vista Data Log Viewer
Web Applications Data Log Viewer

Cause:
Software rounds to the thousandth place.

Resolution:
Confirm that Show Toolbox is checked in Options in the top-left then right-click on the data log viewer that needs to be changed in Vista. Go to the Query tab and click Edit SQL ... Add a ROUND function to the queries, for example

SELECT timestamp
, "Vll ab mean"
, "Vll bc mean"
, "Vll ca mean"

becomes

SELECT timestamp
, ROUND("Vll ab mean", 0) AS "Vll ab mean"
, ROUND("Vll bc mean", 0) AS "Vll bc mean"
, ROUND("Vll ca mean", 0) AS "Vll ca mean"

Save the file. Double-click on the data log viewer and you should see the value is rounded up to the nearest integer.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:
  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger