How can I share a single CT and PT for two or more Meters?

Issue
The User would like to use a PT (potential transformer) or a CT (current transformer) for two separate meters.

Product Line
PowerLogic and ION Meters

Environment
Current Transformers and Potential Transformers

Cause
Typically each power meter has its own set of CT's and PT's. It may be desirable to share a voltage or current source from one of the PT's or CT's.

Resolution
The ION and PM meters can share CTs and PTs with other meters.

In this case the meters will be displaying the same voltage, current and power.  Sometimes this connection may be used in conjunction with a relay.


  • Take PM1200 and three phase 4 wire connection for example, the wiring should be like below:
    Wiring Diagram

    Also,this wiring can be used in other PM and ION meters.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger