Momentum 171CCC98030 Ethernet processor maximum number of concurrent socket connections.

Goals and Symptoms

What is the maximum number of concurrent socket connections?

Causes and Fixes:

A maximum of 96 devices may be communicating with the processor adapter via the Ethernet at any one time.
This 96-device limit consists of:

  • · up to 2 programming panels (one must be in monitor mode)
    · up to 14 general purpose Modbus server paths (ex. Incoming SCADA requests) (Server)
    · up to 16 MSTR elements which support Modbus read, write, or read/write commands (Client)
    · up to 64 cyclic configured data slave paths (I/O Scanner) (Client)

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Schneider Electric Community
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger