Webreach Historical Data gives Pegquery error (80040c8e)

Symptom:
Vista queries work but the same query in Webreach returns:
------------------------------------------------
Webreach error:

"Pegquery error (80040c8e)"

"ActiveX component cannot create object"
"/ion/historical/getlogs.asp line 51"
-----------------------------------------------
This is often due to Vista inheritance issues. To fix:

1) Open Vista
2) Navigate to the Top level window (all the Vista diagrams are linked to each other with Parent-Child relationships)
3) Open the Toolbox and right click on the background
4) Under the Query Server tab select Edit Link> Choose Query1 (or any custom query server)
5) Click OK and save this

After completing the above simple procedure, webreach historical data for this query should work.

Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger