What is the inrush current of the ATV61 High horse power VFDs?
Issue:
Inrush current of the ATV61 / ATV71 High horse power VFDs.
Product Line:
ATV61HC11N4, ATV61HC31N4, ATV61HC25N4, ATV61HC40N4, ATV61HC63N4
ATV71HD90N4, ATV71HC20N4, ATV71HC25N4, ATV71HC31N4, ATV71HC50N4
Environment:
All
Cause:
Application requirement.
Resolution:
Inrush current
Drive power [kW] I peak [A] (~2ms) I peak [A] (~2ms)
Inrush current of the ATV61 / ATV71 High horse power VFDs.
Product Line:
ATV61HC11N4, ATV61HC31N4, ATV61HC25N4, ATV61HC40N4, ATV61HC63N4
ATV71HD90N4, ATV71HC20N4, ATV71HC25N4, ATV71HC31N4, ATV71HC50N4
Environment:
All
Cause:
Application requirement.
Resolution:
Inrush current
Drive power [kW] I peak [A] (~2ms) I peak [A] (~2ms)
ATV71 ATV61 @ 480V +10% @ 400V
90 110 275 208
200 250 556 421
250 315 764 579
310 400 802 608
500 630 1500 1136