How do I disable the Line Contactor on the E-Flex
Issue:
Customer wants to keep the line contactor in the circuit to allow the drive to decelerate verses freewheel stop.
Product Line:
E-Flex
E-Flex with modification B09 (line contactor).
The line contactor opens when the run command is removed.
Place a jumper between terminals 4 and 11. This circuit modification will keep the line contactor closed when the switch is in the AFC position. The line contactor will remain open when the switch is in OFF or BYPASS.
Udgivet til: Schneider Electric Danmark
Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.