Is a line reactor required with a ATV312 600V drives?
Issue:
ATV312 600V drive requirement of a line reactor.
Product Line:
ATV312 ATV31
Environment :
All 575-600V
Cause:
New installation
Resolution:
Yes, a minimum 3% line reactor is required on all 575V / 600V drive installations.