What does error EC02 mean in a Quantum HE CPU ?
Issue:
What does error EC02 mean in a Quantum HE CPU ?
Product Line:
Quantum PLC
Resolution:
EC02 is a failure in the Quantum Operating System. The CPU has encountered a non-maskable interrupt and as a result halted.
One possible cause of the EC02 error is the firmware version on the 140CRP93x 00. To prevent a possible EC02 error during startup the CRP93x must
have firmware version 2.10 or higher.
If the EC02 error is repeatable the CPU should be exchanged.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.