Will the ATV61 or ATV71 drives 4 to 20 ma input speed signal control the drive motor speed between LSP to HSP or 0 to 60hz?
Issue:
ATV61 or ATV71uses 4-20mA input speed signal to control the motor speed between LSP to HSP.
Product Line:
Altivar ATV61
Environment:
All
Cause:
They have low speed LSP set to 45 hz but they want the drives analog input to allow the drive to run between 0 to 60hz not low speed to high speed.
Resolution:
The Drive wills analog inputs will allow the drive to run between Low speed to high speed. If you want to have a low speed setting above 0 and still want the drive to follow 0 to 60hz then set the Reference Template Parameter (BSP) in Menu 1.5 to Pedestal mode.
Menu 1.5 programming below.

ATV61 or ATV71uses 4-20mA input speed signal to control the motor speed between LSP to HSP.
Product Line:
Altivar ATV61
Environment:
All
Cause:
They have low speed LSP set to 45 hz but they want the drives analog input to allow the drive to run between 0 to 60hz not low speed to high speed.
Resolution:
The Drive wills analog inputs will allow the drive to run between Low speed to high speed. If you want to have a low speed setting above 0 and still want the drive to follow 0 to 60hz then set the Reference Template Parameter (BSP) in Menu 1.5 to Pedestal mode.
Menu 1.5 programming below.
Udgivet til: Schneider Electric Danmark




Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.