Is the BCPME Natively Supported in PME?
Issue:
Is the BCPME Natively Supported in Power Monitoring Expert?
Product Line:
Power Monitoring Expert 7.2.2
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Environment:
Configuring the BCPME meter in Power Monitoring Expert software
Cause:
The user wants to know how to configure the BCPME in PME software
Resolution:
PME does not have a specific driver for BCPME. Therefore, the user will have to use the BCPM driver for BCPME.
- Add the site using the BCPME IP address.
- Create a device underneath that site as a "serial device on an Ethernet gateway" using the BCPM device type
- Enter unit ID 100 for Modbus TCP.
(NOTE: The BCPME is the same as the normal BCPM A, B, and C types with the exception that an ethernet gateway is embedded into the physical device and onboard logging (a 1-deep data recorder))
Udgivet til: Schneider Electric Danmark








Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.