Cannot View diagrams in engineering client after running EPSS Generator tool
Issue
Diagrams created from the EPSS generator tool will not open in the engineering client; Diagrams open fine in Vista from the server.
Product Line
PMEHC 7.22
PMEDC 7.22
PME 8, 8.1, 8.2
Environment
StruxureWare Power Monitoring Expert Vista Application (7.22, 8, 8.1, & 8.2)
Cause
EPSS Generator tool does not bring the network path over for the diagrams. Right-clicking on the link in vista will show the local server path for the diagrams "C:\Program files(X86)\Schneider Electric\Power Monitoring Expert\config\diagrams\ud\EPSS\diagram.dmg"
Resolution
1. In Vista engineering client, click "File > Open" you will see the server path to the diagrams. You can copy this or note it.
2. Right-click on the link in the engineering client and then select the action tab in the path field.
3. Remove the local path EG, "C:\Program files(X86)\Schneider Electric\Power Monitoring Expert\config\diagrams\ud\EPSS\diagram.dmg", keeping the diagram name and past the server path you copied, it will now look something like this:
"\\Powerlogic02\ION-Ent\config\diagrams\ud\EPSS\diagram.dgm"
4. You will need to do this for each link created by the generator tool.
Udgivet til: Schneider Electric Danmark
Brug for hjælp?
Produktvælger
Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.
Få et tilbud
Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.
Find forhandler
Find den nærmeste Schneider Electric-distributør.
Hjælpecenter
Find supportressourcer til alle dine behov på ét sted.