Issue:
3 wire control setup on an ATV12
Product Line:
Altivar ATV12
Environment:
All
Cause:
He has 2 momentary pushbuttons 1 NC for stop and 1 NO for start
Resolution:
Arrow down to the FULL menu enter
Arrow down to IO menu enter
find tCC enter and set this to 3C ( you will need to hold the enter button for 3 seconds before it will change from 2C to 3C)
3 wire control setup on an ATV12
Product Line:
Altivar ATV12
Environment:
All
Cause:
He has 2 momentary pushbuttons 1 NC for stop and 1 NO for start
Resolution:
Arrow down to the FULL menu enter
Arrow down to IO menu enter
find tCC enter and set this to 3C ( you will need to hold the enter button for 3 seconds before it will change from 2C to 3C)