Why would I see Output Phase Loss on my E-flex system that is equipped with Bypass (Power circuit Y)?
Issue:
Possible cause of an Output Phase Loss on an E-flex system that is equipped with Bypass (Power circuit Y)

Product Line:
8839EFD* E-flex systems.

Environment:
Units equipped with power circuit Y (Full voltage bypass)

Cause:
Customer is seeing random Output Phase Loss faults with no apparent cause.

Resolution:
Output Phase Loss faults should not be indicated on an E-flex system with Full Voltage Bypass.   Under menu 1.8, Fault management menu, Output Phase Loss should be disabled on E-flex systems, with the bypass contactor.  This should be disabled from the factory to prevent a known condition where Output Phase Fault can be improperly triggered in E-flex systems equipped with full voltage bypass contactors.  Phase loss protection for the motor is provided by other components within the E-flex system in this particular configuration.


Schneider Electric Danmark

Se mere
Område:
Se mere
Område:

Brug for hjælp?

  • Produktvælger

    Find hurtigt og nemt de rette produkter og det rette tilbehør til dine anvendelser.

  • Få et tilbud

    Start din salgsforespørgsel online, så vil du blive kontaktet af en ekspert.

  • Find forhandler

    Find den nærmeste Schneider Electric-distributør.

  • Hjælpecenter

    Find supportressourcer til alle dine behov på ét sted.

  • Produktdokumentation
  • Download af software
  • Produktvælger
  • Udskiftning og erstatning af produkter
  • Hjælp og kontaktcenter
  • Find forhandler
  • Få et tilbud
  • Find vores kontorer
  • Karriere
  • Virksomhedsprofil
  • Rapportér en forseelse
  • Tilgængelighed
  • Presserum
  • Investorer
  • EcoStruxure
  • Jobsøgning
  • Blog
  • Privatlivspolitik
  • Cookiemeddelelse
  • Vilkår for anvendelse
  • Rediger dine cookieindstillinger