How to resolve the E5006 failure during Unity application upload.
Question:
Customer met with E5006 failure during Unity application upload. What's the root cause & how to solve it?
Answer:
The application is corrupted in the PLC ( the conf tree is Invalid )
There are 2 ways to restore :
1. If the user has saved correctly the application before ( it seems that it is not the case ) , rebuild all the application to FIX then, download ( using Current Unity Version )
2. The customer (or support ) can use old Unity version to upload application. Then must rebuild all to fix the problem (save to STA ) or export (to XEF) and finally use current version to re open ( STA or XEF )
Customer met with E5006 failure during Unity application upload. What's the root cause & how to solve it?
Answer:
The application is corrupted in the PLC ( the conf tree is Invalid )
There are 2 ways to restore :
1. If the user has saved correctly the application before ( it seems that it is not the case ) , rebuild all the application to FIX then, download ( using Current Unity Version )
2. The customer (or support ) can use old Unity version to upload application. Then must rebuild all to fix the problem (save to STA ) or export (to XEF) and finally use current version to re open ( STA or XEF )